BNS 160kW - 320kW
  • ŸŸPure sine wave output.
  • ŸŸ4-layer PCB, and SMD technology.
  • ŸŸŸŸHigh efficiency IGBT inverter technology.
  • ŸŸŸOutput isolated transformer for heavy duty load.
  • ŸThree phase AC output, support 100% unbalanced load.
  • ŸŸIntelligent battery management and temperature compensation function.
  • ŸCapable of driving inductive & capacitive load from starting.
  • ŸLCD touch screen display.
  • ŸComplete protections.
  • Ÿ92% system efficiency.
  • ŸStrong environment adaptability.
  • ŸTemperature sensor controlled cooling fan.

MODEL

BNS 160kW

BNS 200kW

BNS 320kW

Capacity

160KW

200KW

320KW

PV INPUT 

Input voltage range

380/400/415 Vac ± 20%, 3 phase and 4 wire

Input frequency

50/60 Hz ± 10%

AC OUTPUT

Voltage

380/400/415Vac ±2%

Frequency

50/60Hz ±0.5%

Crest factor

3 : 1

Efficiency

> 99% in city power mode; > 80% in inverter mode

Transfer Time

0

Waveform

Pure Sine Wave

Power factor

0.8 – 1 lagging

THD

< 3% on linear load, < 5% on nonlinear load

Overload capability

105% - 110% for 10mins; 110% - 125% for 1 min, > 125% for 10s

BATTERY

Type

Maintenance free lead-acid cell

DC voltage

384Vdc (12Vdc x 32pc)

396Vdc (12Vdc x 33pc)

Charge current

6 - 30 A

SYSTEM & ENVIRONMENTAL

Efficiency

>96%

>94%

Cooling method

Temperature cooling fan

Noise

< 63db (1 Meter)

Operating temperature

0°C to +40°C (> 50°C derating)

Humidity 

0-90% (non-condensing)

Operation altitude

< 5000m (> 2000m derating)

LCD display contents

Operating status, menu operation, voltage, current, parameter, model

LED display contents

Inverter operation, rectification error, operation error

Communication interface

RS485, dry contact

Electrical protections

Input over/under voltage, output over/under voltage, overload, short circuit, over temperature, reverse polarity, lighting surge protection

PHYSICAL

Dimension (WxHxD) (mm)

1000x900x1680

1600x980x1800

N.W./G.W. (kg)

950/1010

2100/2200

2500/2600

*Specifications are subject to change without prior notice.